CHAPTER
6: PLUMBING ELEMENTS AND FACILITIES |
|
ANSI
Chapter 6. Plumbing Elements and Facilities |
||
|
601
General |
|
ANSI
601 General |
||
|
601.1
Scope. The provisions of Chapter 6 shall apply where
required by Chapter 2 or where referenced by a requirement in this document. |
|
ANSI
601.1 Scope. Plumbing elements and facilities required to be
accessible by scoping provisions adopted by the administrative authority
shall comply with the applicable provisions of Chapter 6. |
||
|
602
Drinking Fountains |
4.15 Drinking Fountains
and Water Coolers. |
ANSI
602 Drinking Fountains |
||
|
602.1
General. Drinking fountains shall comply with 307 and
602. |
4.15.1Minimum Number. Drinking
fountains or water coolers required to be accessible by 4.1 shall comply with
4.15. |
ANSI
602.1 General. Accessible drinking fountains shall comply with
Sections 602 and 307. |
||
|
602.2
Clear Floor Space. Units shall have a clear floor or ground space
complying with 305 positioned for a forward approach and centered on the
unit. Knee and toe clearance complying with 306 shall be provided. EXCEPTION: A
parallel approach complying with 305 shall be permitted at units for
children's use where the spout is 30 inches (760 mm) maximum above the finish
floor or ground and is 3 1/2 inches (90 mm) maximum from the front edge of
the unit, including bumpers. |
4.15.5 Clearances. (1)
Wall- and post-mounted cantilevered units shall have a clear knee space
between the bottom of the apron and the floor or ground at least 27 in (685
mm) high, 30 in (760 mm) wide, and 17 in to 19 in (430 mm to 485 mm) deep (see
Fig. 27(a) and (b)). Such units shall also have a minimum clear floor space
30 in by 48 in (760 mm by 1220 mm) to allow a person in a wheelchair to
approach the unit facing forward. See also Appendix 4.15.5 (2) Free-standing or built-in units not having a
clear space under them shall have a clear floor space at least 30 in by 48 in
(760 mm by 1220 mm) that allows a person in a wheelchair to make a parallel
approach to the unit (see Fig. 27(c) and (d)). This clear floor space shall
comply with 4.2.4. NOTE: Figure
27(a) indicates that, in addition to clearances discussed in the text, the
following knee clearance is required underneath the fountain: 27 inches (685
mm) minimum from the floor to the underside of the fountain which extends 8
inches (205 mm) minimum measured from the front edge underneath the fountain
back towards the wall; if a minimum 9 inches (230 mm) of toe clearance is
provided, a maximum of 6 inches (150 mm) of the 48 inches (1220 mm) of clear
floor space required at the fixture may extend into the toe space. (4.15.2,
4.15.5) Figure 27(b) show a 48
inch (1220 mm) minimum by 30 inch (760 mm) minimum clear floor space is
required for a forward approach to a wall-mounted fountain. If the
wall-mounted fountain is in an alcove, the minimum width of the alcove is 30
inches (760 mm) and the depth is 24 inches (610 mm) maximum. Figure 27(c) illustrates a free-standing
fountain or cooler. A 48 inch (1220 mm) minimum by 30 inch (760 mm)
minimum clear floor space is required for a side approach (long side parallel
to the front of the fountain or cooler). Figure 27(d) shows a built-in fountain or
cooler. A 48 inch (1220 mm) minimum by 30 inch (760 mm)
minimum clear floor space is required for a side approach (long side parallel
to the front of the fountain or cooler). The recess for the fountain is not
to exceed the fountain depth. |
ANSI
602.2 Clear Floor Space. A clear floor space complying with
Section 305, positioned for a forward approach to the drinking fountain,
shall be provided. Knee and toe space complying with Section 306 shall be
provided. The clear floor space shall be centered on the drinking fountain. EXCEPTIONS: 1. Drinking fountains for standing persons. 2. Drinking fountains primarily for children’s
use shall be permitted where the spout is 30 inches (760 mm) maximum above
the floor, and a parallel approach complying with Section 305, centered on
the drinking fountain, is provided. 305, centered on the drinking fountain, shall be
permitted. 3. In existing buildings, existing drinking
fountains providing a parallel approach complying with Section 305, centered
on the drinking fountain, shall be permitted. 4. Where specifically permitted by the
administrative authority, a parallel approach complying with Section 305,
centered on the drinking fountain, shall be permitted for drinking fountains
that replace existing drinking fountains with a parallel approach. |
||
|
602.3
Operable Parts. Operable parts shall comply with 309. |
4.15.4 Controls. Controls
shall comply with 4.27.4. Unit controls shall be front mounted or side
mounted near the front edge. |
ANSI
602.3 Operable Parts. Operable parts shall comply with Section
309. |
||
|
602.4
Spout Height. Spout outlets shall be 36 inches (915 mm) maximum
above the finish floor or ground. |
4.15.2 Spout Height.
Spouts shall be no higher than 36 in (915 mm), measured from the floor or
ground surfaces to the spout outlet (see Fig. 27(a)). |
ANSI
602.4 Spout Outlet Height. Spout outlets of wheelchair accessible
drinking fountains shall be 36 inches (915 mm) maximum above the floor. Spout
outlets of drinking fountains for standing persons shall be 38 inches (965
mm) minimum and 43 inches (1090 mm) maximum above the floor. |
||
|
602.5
Spout Location. The spout shall be located 15 inches (380 mm)
minimum from the vertical support and 5 inches (125 mm) maximum from the
front edge of the unit, including bumpers. |
4.15.3 Spout Location. The
spouts of drinking fountains and water coolers shall be at the front of the
unit and shall direct the water flow in a trajectory that is parallel or
nearly parallel to the front of the unit. The spout shall provide a flow of
water at least 4 in (100 mm) high so as to allow the insertion of a cup or
glass under the flow of water. On an accessible drinking fountain with a
round or oval bowl, the spout must be positioned so the flow of water is
within 3 in (75 mm) of the front edge of the fountain. |
ANSI
602.5 Spout Location. The spout shall be located 15 inches
(380 mm) minimum from the vertical support and 5 inches (125 mm) maximum from
the front edge of the drinking fountain, including bumpers. Where only a
parallel approach is provided, the spout shall be located 31/2 inches (89 mm)
maximum from the front edge of the drinking fountain, including bumpers. |
||
|
602.6
Water Flow. The spout shall provide a flow of water 4 inches
(100 mm) high minimum and shall be located 5 inches (125 mm) maximum from the
front of the unit. The angle of the water stream shall be measured
horizontally relative to the front face of the unit. Where spouts are located
less than 3 inches (75 mm) of the front of the unit, the angle of the water
stream shall be 30 degrees maximum. Where spouts are located between 3 inches
(75 mm) and 5 inches (125 mm) maximum from the front of the unit, the angle
of the water stream shall be 15 degrees maximum. |
ANSI
602.6 Water Flow. The spout shall provide a flow of water 4 inches
(102 mm) minimum in height. The angle of the water stream from spouts within
3 inches (76 mm) of the front of the drinking fountain shall be 30 degrees
maximum, and from spouts between 3 inches (76 mm) and 5 inches (125 mm) from
the front of the drinking fountain shall be 15 degrees maximum, measured
horizontally relative to the front face of the drinking fountain. |
|||
|
602.7
Drinking Fountains for Standing Persons. Spout outlets of
drinking fountains for standing persons shall be 38 inches (965 mm) minimum
and 43 inches (1090 mm) maximum above the finish floor or ground. |
|
|
||
|
603
Toilet and Bathing Rooms |
|
ANSI
603 Toilet and Bathing Rooms |
||
|
4.23 Bathrooms, Bathing Facilities, and Shower
Rooms. |
||||
|
603.1
General. Toilet and bathing rooms shall comply with 603. |
4.22.1 Minimum Number.
Toilet facilities required to be accessible by 4.1 shall comply with 4.22.
Accessible toilet rooms shall be on an accessible route. |
ANSI
603.1 General. Accessible toilet and bathing rooms shall comply
with Section 603. |
||
|
4.23.1 Minimum Number. Bathrooms,
bathing facilities, or shower rooms required to be accessible by 4.1 shall
comply with 4.23 and shall be on an accessible route. |
||||
|
603.2
Clearances. Clearances shall comply with 603.2. |
4.22.3 Clear Floor Space
[Toilet Rooms]. The accessible fixtures and controls required
in 4.22.4, 4.22.5, 4.22.6, and 4.22.7 shall be on an accessible route. An
unobstructed turning space complying with 4.2.3 shall be provided within an
accessible toilet room. The clear floor space at fixtures and controls, the
accessible route, and the turning space may overlap. 4.23.3 Clear Floor Space
[Bathrooms, Bathing Facilities, and Shower Rooms]. The accessible
fixtures and controls required in 4.23.4, 4.23.5, 4.23.6, 4.23.7, 4.23.8, and
4.23.9 shall be on an accessible route. An unobstructed turning space
complying with 4.2.3 shall be provided within an accessible bathroom. The
clear floor spaces at fixtures and controls, the accessible route, and the
turning space may overlap. |
ANSI
603.2 Clearances. |
||
|
603.2.1
Turning Space. Turning space complying with 304 shall be
provided within the room. |
ANSI
603.2.1 Turning Space. A turning space complying with Section
304 shall be provided within the room. |
|||
|
603.2.2
Overlap. Required clear floor spaces, clearance at
fixtures, and turning space shall be permitted to overlap. |
ANSI
603.2.2 Overlap. Clear floor spaces, clearances at fixtures, and
turning spaces shall be permitted to overlap. |
|||
|
603.2.3
Door Swing. Doors shall not swing into the clear floor space
or clearance required for any fixture. Doors shall be permitted to swing into
the required turning space. EXCEPTIONS: 1. Doors to a toilet room or bathing room for a
single occupant accessed only through a private office and not for common use
or public use shall be permitted to swing into the clear floor space or
clearance provided the swing of the door can be reversed to comply with
603.2.3. 2. Where the toilet room or bathing room is for
individual use and a clear floor space complying with 305.3 is provided
within the room beyond the arc of the door swing, doors shall be permitted to
swing into the clear floor space or clearance required for any fixture. |
4.22.2 Doors [Toilet Rooms].
All doors to accessible toilet rooms shall comply with 4.13. Doors shall not
swing into the clear floor space required for any fixture. |
ANSI
603.2.3 Door Swing. Doors shall not swing into the clear
floor space or clearance for any fixture. EXCEPTIONS:
1. Doors to a toilet and bathing room for a
single occupant, accessed only through a private office and not for common
use or public use shall be permitted to swing into the clear floor space,
provided the swing of the door can be reversed to meet Section 603.2.3. 2. Where the room is for individual use and a
clear floor space complying with Section 305.3 is provided within the room
beyond the arc of the door swing. |
||
|
4.23.2 Doors Space [Bathrooms,
Bathing Facilities, and Shower Rooms]. Doors to accessible bathrooms shall
comply with 4.13. Doors shall not swing into the floor space required for any
fixture. |
||||
|
603.3
Mirrors. Mirrors located above lavatories or countertops
shall be installed with the bottom edge of the reflecting surface 40 inches
(1015 mm) maximum above the finish floor or ground. Mirrors not located above
lavatories or countertops shall be installed with the bottom edge of the
reflecting surface 35 inches (890 mm) maximum above the finish floor or
ground. |
4.22.6 Lavatories and
Mirrors[Toilet Rooms]. If lavatories and mirrors are provided,
then at least one of each shall comply with 4.19. |
ANSI
603.3 Mirrors. Mirrors located above lavatories, sinks or
counters shall be mounted with the bottom edge of the reflecting surface 40
inches (1015 mm) maximum above the floor. Mirrors not located above
lavatories, sinks or counters shall be mounted with the bottom edge of the
reflecting surface 35 inches (890 mm) maximum above the floor. |
||
|
4.23.6 Lavatories and Mirrors
Space [Bathrooms, Bathing Facilities, and Shower Rooms]. If lavatories
and mirrors are provided, then at least one of each shall comply with 4.19. |
||||
|
4.19.6 Mirrors. Mirrors
shall be mounted with the bottom edge of the reflecting surface no higher
than 40 in (1015 mm) above the finish floor (see Fig. 31). |
||||
|
603.4
Coat Hooks and Shelves. Coat hooks shall be located within one
of the reach ranges specified in 308. Shelves shall be located 40 inches
(1015 mm) minimum and 48 inches (1220 mm) maximum above the finish floor. |
|
ANSI
603.4 Coat Hooks and Shelves. Coat hooks shall be located
within one of the reach ranges specified in Section 308. Shelves shall be 40
inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the floor. |
||
|
604
Water Closets and Toilet Compartments |
ANSI
604 Water Closets and Toilet Compartments |
|||
|
4.17
Toilet Stalls. |
||||
|
604.1
General. Water closets and toilet compartments shall
comply with 604.2 through 604.8. EXCEPTION: Water
closets and toilet compartments for children's use shall be permitted to
comply with 604.9. |
4.16.1
General. Accessible water closets shall comply with
4.16.2 through 4.16.6. See also Appendix 4.16.1 |
ANSI
604.1 General. Accessible water closets and toilet compartments
shall comply with Section 604. Compartments containing more than one plumbing
fixture shall comply with Section 603. Wheelchair accessible compartments
shall comply with Section 604.8. Ambulatory accessible compartments shall
comply with Section 604.9. EXCEPTION:
Water closets and toilet compartments primarily for children’s use shall be
permitted to comply with Section 604.10 as applicable. |
||
|
4.17.1
Location. Accessible toilet stalls shall be on an
accessible route and shall meet the requirements of 4.17.2 through 4.17.6. 4.17.2
Water Closets. Water closets in accessible stalls shall comply
with 4.16. See also Appendix 4.17.1 |
||||
|
604.2
Location. The water closet shall be positioned with a wall
or partition to the rear and to one side. The centerline of the water closet
shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the
side wall or partition, except that the water closet shall be 17 inches (430
mm) minimum and 19 inches (485 mm) maximum from the side wall or partition in
the ambulatory accessible toilet compartment specified in 604.8.2. Water
closets shall be arranged for a left-hand or right-hand approach. |
4.16.2 Clear Floor Space.
Clear floor space for water closets not in stalls shall comply with Fig. 28.
Clear floor space may be arranged to allow either a left-handed or
right-handed approach. NOTE: Figure 28 shows that for a front transfer to the
water closet, the minimum clear floor space at the water closet is a minimum
48 inches (1220 mm) in width by a minimum of 66 inches (1675 mm) in length.
For a diagonal transfer to the water closet, the minimum clear floor space is
a minimum of 48 inches (1220 mm) in width by a minimum of 56 inches (1420 mm)
in length. For a side transfer to the water closet, the minimum clear floor
space is a minimum of 60 inches (1525 mm) in width by a minimum of 56 inches
(1420 mm) in length. (4.16.2, A4.22.3) |
ANSI
604.2 Location. The water closet shall be located with a wall or
partition to the rear and to one side. The centerline of the water closet
shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the
side wall or partition. Water closets located in ambulatory accessible
compartments specified in Section 604.9 shall have the centerline of the
water closet 17 inches (430 mm) minimum to 19 inches (485 mm) maximum from
the side wall or partition. |
||
|
604.3
Clearance. Clearances around water closets and in toilet
compartments shall comply with 604.3. |
ANSI
604.3 Clearance. |
|||
|
604.3.1
Size. Clearance around a water closet shall be 60 inches (1525 mm) minimum
measured perpendicular from the side wall and 56 inches (1420 mm) minimum
measured perpendicular from the rear wall. |
ANSI
604.3.1 Size. A clearance around a water closet 60 inches
(1525 mm) minimum, measured perpendicular from the sidewall, and 56 inches
(1420 mm) minimum, measured perpendicular from the rear wall, shall be
provided. |
|||
|
604.3.2
Overlap. The required clearance around the water closet
shall be permitted to overlap the water closet, associated grab bars,
dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible
routes, clear floor space and clearances required at other fixtures, and the
turning space. No other fixtures or obstructions shall be located within the
required water closet clearance. EXCEPTION: In
residential dwelling units, a lavatory complying with 606 shall be permitted
on the rear wall 18 inches (455 mm) minimum from the water closet centerline
where the clearance at the water closet is 66 inches (1675 mm) minimum
measured perpendicular from the rear wall. |
ANSI
604.3.2 Overlap. The required clearance around the water closet
shall be permitted to overlap the water closet, associated grab bars, paper
dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible
routes, clear floor space at other fixtures and the turning space. No other
fixtures or obstructions shall be within the required water closet clearance. |
|||
|
604.4
Seats. The seat height of a water closet above the
finish floor shall be 17 inches (430 mm) minimum and 19 inches (485 mm)
maximum measured to the top of the seat. Seats shall not be sprung to return
to a lifted position. EXCEPTIONS:
1. A water closet in a toilet room for a single
occupant accessed only through a private office and not for common use or
public use shall not be required to comply with 604.4. 2. In residential dwelling units, the height of
water closets shall be permitted to be 15 inches (380 mm) minimum and 19
inches (485 mm) maximum above the finish floor measured to the top of the
seat. |
4.16.3 Height. The height of
water closets shall be 17 in to 19 in (430 mm to 485 mm), measured to the top
of the toilet seat (see Fig. 29(b)). Seats shall not be sprung to return to a
lifted position. Note: In Figure 29(b) the top of the seat of the
water closet is 17 in to 19 in (430 mm to 485 mm). |
ANSI
604.4 Height. The height of water closet seats shall be 17
inches (430 mm) minimum and 19 inches (485 mm) maximum above the floor,
measured to the top of the seat. Seats shall not be sprung to return to a
lifted position. EXCEPTION: A
water closet in a toilet room for a single occupant, accessed only through a
private office and not for common use or public use, shall not be required to
comply with Section 604.4. |
||
|
604.5
Grab Bars. Grab bars for water closets shall comply with
609. Grab bars shall be provided on the side wall closest to the water closet
and on the rear wall. EXCEPTIONS: 1. Grab bars shall not be required to be
installed in a toilet room for a single occupant accessed only through a
private office and not for common use or public use provided that
reinforcement has been installed in walls and located so as to permit the
installation of grab bars complying with 604.5. 2. In residential dwelling units, grab bars shall
not be required to be installed in toilet or bathrooms provided that
reinforcement has been installed in walls and located so as to permit the
installation of grab bars complying with 604.5. 3. In detention or correction facilities, grab
bars shall not be required to be installed in housing or holding cells that
are specially designed without protrusions for purposes of suicide
prevention. |
4.16.4 Grab Bars.
Grab bars for water closets not located in stalls shall comply with 4.26 and
Fig. 29. The grab bar behind the water closet shall be 36 in (915 mm)
minimum. |
ANSI
604.5 Grab Bars. Grab bars for water closets shall comply with
Section 609 and shall be provided in accordance with Sections 604.5.1 and
604.5.2. Grab bars shall be provided on the rear wall and on the side wall
closest to the water closet. EXCEPTIONS: 1. Grab bars are not required to be installed in
a toilet room for a single occupant, accessed only through a private office
and not for common use or public use, provided reinforcement has been
installed in walls and located so as to permit the installation of grab bars
complying with Section 604.5. 2. In
detention or correction facilities, grab bars are not required to be
installed in housing or holding cells or rooms that are specially designed
without protrusions for purposes of suicide prevention. 3. In Type
A units, grab bars are not required to be installed where reinforcement
complying with Section 1003.11.4 is installed for the future installation of
grab bars. 4. In Type B units located in institutional
facilities and assisted living facilities, two swing–up grab bars shall be
permitted to be installed in lieu of the rear wall and side wall grab bars.
Swing–up grab bars shall comply with Sections 604.5.3 and 609. 5. In a Type B unit, where fixtures are located
on both sides of the water closet, a swing–up grab bar complying with
Sections 604.5.3 and 609 shall be permitted. The swing–up grab bar shall be
installed on the side of the water closet with the 18 inch (455 mm) clearance
required by Section 1004.11.3.1.2. |
||
|
604.5.1
Side Wall. The side wall grab bar shall be 42 inches (1065
mm) long minimum, located 12 inches (305 mm) maximum from the rear wall and
extending 54 inches (1370 mm) minimum from the rear wall. |
Note: In Figure 29(a) a 36 inches (915 mm)
minimum length grab bar, mounted 33-36 inches (840-915 mm) above the finish
floor, is required behind the water closet. The grab bar must extend at least
12 inches (305 mm) from the centerline of the water closet toward the side
wall and at least 24 inches (610 mm) from the centerline of the water closet
toward the open side. In Figure 29(b) a 42 inch
(1065 mm) minimum length grab bar is required to the side of the water closet
spaced 12 inches (305 mm) maximum from the back wall and extending a minimum
of 54 inches (1370 mm) from the back wall at a height between 33 and 36
inches (840-915 mm). The toilet paper dispenser shall be mounted at a minimum
height of 19 inches (485 mm). (4.16.3, 4.16.4, 4.16.6) |
ANSI
604.5.1 Fixed Side Wall Grab Bars. Fixed sidewall grab bars
shall be 42 inches (1065 mm) minimum in length, located 12 inches (305 mm)
maximum from the rear wall and extending 54 inches (1370 mm) minimum from the
rear wall. In addition, a vertical grab bar 18 inches (455 mm) minimum in
length shall be mounted with the bottom of the bar located between 39 inches
(990 mm) and 41 inches (1040 mm) above the floor, and with the center line of
the bar located between 39 inches (990 mm) and 41 inches (1040 mm) from the
rear wall. EXCEPTIONS: 1. In Type A and Type B units, the vertical grab
bar component is not required. 2. In a Type B unit, when a side wall is not
available for a 42–inch (1065 mm) grab bar, the sidewall grab bar shall be
permitted to be 18 inches (455 mm)
minimum in length, located 12 inches (305 mm) maximum from the rear wall and
extending 30 inches (760 mm) minimum from the rear wall. |
||
|
604.5.2
Rear Wall. The rear wall grab bar shall be 36 inches (915
mm) long minimum and extend from the centerline of the water closet 12 inches
(305 mm) minimum on one side and 24 inches (610 mm) minimum on the other
side. EXCEPTIONS: 1. The rear grab bar shall be permitted to be 24
inches (610 mm) long minimum, centered on the water closet, where wall space
does not permit a length of 36 inches (915 mm) minimum due to the location of
a recessed fixture adjacent to the water closet. 2. Where an administrative authority requires
flush controls for flush valves to be located in a position that conflicts
with the location of the rear grab bar, then the rear grab bar shall be
permitted to be split or shifted to the open side of the toilet area. |
NOTE: In Figure 29(a) a 36 inch (915 mm) minimum length
grab bar is required behind the water closet mounted at a height between 33
and 36 inches (840-915 mm). The grab bar must extend a minimum of 12 inches
(305) beyond the center of the water closet toward the side wall and a
minimum of 24 inches (610 mm) toward the open side for either a left or right
side approach. Figure 30(c) indicates the
grab bar on the back wall shall be 36 inches minimum in length, extending
from the wall toward the open side of the water closet, 33-36 inches above
the finish floor. |
ANSI
604.5.2 Rear Wall Grab Bars. The rear wall grab bar shall
be 36 inches (915 mm) minimum in length, and extend from the centerline of
the water closet 12 inches (305 mm) minimum on the side closest to the wall,
and 24 inches (610 mm) minimum on the transfer side. EXCEPTIONS: 1. The rear grab bar shall be permitted to be 24
inches (610 mm) minimum in length, centered on the water closet, where wall
space does not permit a grab bar 36 inches (915 mm) minimum in length due to
the location of a recessed fixture adjacent to the water closet. 2. In a Type A or Type B unit, the rear grab bar
shall be permitted to be 24 inches (610 mm) minimum in length, centered on
the water closet, where wall space does not permit a grab bar 36 inches (915
mm) minimum in length. 3. Where an administrative authority requires
flush controls for flush valves to be located in a position that conflicts
with the location of the rear grab bar, that grab bar shall be permitted to
be split or shifted to the open side of the toilet area. |
||
|
|
|
ANSI
604.5.3 Swing–up Grab Bars. Where swing–up grab bars are
installed, a clearance of 18 inches (455 mm) minimum from the centerline of
the water closet to any side wall or obstruction shall be provided. A
swing–up grab bar shall be installed with the centerline of the grab bar
153/4 inches (400 mm) from the centerline of the water closet. Swing–up grab
bars shall be 28 inches (710 mm) minimum in length, measured from the wall to
the end of the horizontal portion of the grab bar. |
||
|
604.6
Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with 309. Flush controls
shall be located on the open side of the water closet except in ambulatory
accessible compartments complying with 604.8.2. |
4.16.5 Flush Controls. Flush
controls shall be hand operated or automatic and shall comply with 4.27.4.
Controls for flush valves shall be mounted on the wide side of toilet areas
no more than 44 in (1120 mm) above the floor. |
ANSI
604.6 Flush Controls. Flush controls shall be hand operated or
automatic. Hand operated flush controls shall comply with Section 309. Flush
controls shall be located on the open side of the water closet. EXCEPTION: In
ambulatory accessible compartments complying with Section 604.9, flush
controls shall be permitted to be located on either side of the water closet. |
||
|
604.7
Dispensers. Toilet
paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm)
minimum and 9 inches (230 mm) maximum in front of the water closet measured
to the centerline of the dispenser. The outlet of the dispenser shall be 15
inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish
floor and shall not be located behind grab bars. Dispensers shall not be of a
type that controls delivery or that does not allow continuous paper flow. |
4.16.6 Dispensers. Toilet
paper dispensers shall be installed within reach, as shown in Fig. 29(b).
Dispensers that control delivery, or that do not permit continuous paper
flow, shall not be used. NOTE: In
Figure 29(b) the toilet paper dispenser is required to be mounted at a
minimum height of 19 inches (485 mm). (4.16.3, 4.16.4, 4.16.6) |
ANSI
604.7 Dispensers. Toilet paper dispensers shall comply with
Section 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm)
maximum in front of the water closet measured to the centerline of the
dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum
and 48 inches (1220 mm) maximum above the floor, and shall not be located
behind the grab bars. Dispensers shall not be of a type that control
delivery, or do not allow continuous paper flow. |
||
|
604.8
Toilet Compartments. Wheelchair accessible toilet
compartments shall meet the requirements of 604.8.1 and 604.8.3. Compartments
containing more than one plumbing fixture shall comply with 603. Ambulatory
accessible compartments shall comply with 604.8.2 and 604.8.3. |
|
|
||
|
604.8.1
Wheelchair Accessible Compartments. Wheelchair accessible
compartments shall comply with 604.8.1. |
|
ANSI
604.8 Wheelchair Accessible Compartments. |
||
|
ANSI
604.8.1 General. Wheelchair accessible compartments shall comply
with Section 604.8. |
||||
|
604.8.1.1
Size. Wheelchair accessible compartments shall be 60
inches (1525 mm) wide minimum measured perpendicular to the side wall, and 56
inches (1420 mm) deep minimum for wall hung water closets and 59 inches (1500
mm) deep minimum for floor mounted water closets measured perpendicular to
the rear wall. Wheelchair accessible compartments for children's use shall be
60 inches (1525 mm) wide minimum measured perpendicular to the side wall, and
59 inches (1500 mm) deep minimum for wall hung and floor mounted water
closets measured perpendicular to the rear wall. |
4.17.3 Size
and Arrangement. The size and arrangement of the standard toilet stall
shall comply with Fig. 30(a), Standard Stall. Standard toilet stalls with a
minimum depth of 56 in (1420 mm) (see Fig. 30(a)) shall have wall-mounted
water closets. If the depth of a standard toilet stall is increased at least
3 in (75 mm), then a floor-mounted water closet may be used. Arrangements
shown for standard toilet stalls may be reversed to allow either a left- or
right-hand approach. Additional stalls shall be provided in conformance with
4.22.4. EXCEPTION: In instances of alteration
work where provision of a standard stall (Fig. 30(a)) is technically
infeasible or where plumbing code requirements prevent combining existing
stalls to provide space, either alternate stall (Fig. 30(b)) may be provided
in lieu of the standard stall. NOTE: In Figure 30(a), the location of the door is illustrated to be in
front of the clear space (next to the water closet), with a maximum stile
width of 4 inches (100 mm). An alternate door location is illustrated to be
on the side of the toilet stall with a maximum stile width of 4 inches (100
mm). The minimum width of the standard stall shall be 60 inches (1525 mm).
The centerline of the water closet shall be 18 inches (455 mm) from the side
wall. Figure 30(a-1) indicates that where a standard stall is provided at
the end of a row of stalls, the door (if located on the side of the stall)
may swing into to the stall, if the length of the stall is extended at least
a minimum of 36 inches (915 mm) beyond the required minimum length. In
Figure 30(b), two alternate stalls are
illustrated; one alternate stall is required to be 36 inches (915 mm) in
width. The other alternate stall is required to be a minimum of 48 inches
(1220 mm) in width. If a wall mounted water closet is used, the depth of the
stall is required to be a minimum of 66 inches (1675 mm). If a floor mounted
water closet is used, the depth of the stall is required to be a minimum of
69 inches (1745 mm). The 36 inch wide stall shall have parallel grab bars on
the side walls. The 48 inch minimum stall shall have a grab bar behind the
water closet and one on the side wall next to the water closet. In each
alternate, the centerline of the water closet is 18 inches (455 mm) from a
side wall. |
ANSI
604.8.2 Size. The minimum area of a wheelchair accessible
compartment shall be 60 inches (1525 mm) minimum in width measured
perpendicular to the side wall, and 56 inches (1420 mm) minimum in depth for wall
hung water closets, and 59 inches (1500 mm) minimum in depth for floor
mounted water closets measured perpendicular to the rear wall. The minimum
area of a wheelchair accessible compartment for primarily children’s use
shall be 60 inches (1525 mm) minimum in width measured perpendicular to the
side wall, and 59 inches (1500 mm) minimum in depth for wall hung and floor
mounted water closets measured perpendicular to the rear wall. |
||
|
604.8.1.2
Doors. Toilet compartment doors, including door hardware,
shall comply with 404 except that if the approach is to the latch side of the
compartment door, clearance between the door side of the compartment and any
obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in
the front partition or in the side wall or partition farthest from the water
closet. Where located in the front partition, the door opening shall be 4
inches (100 mm) maximum from the side wall or partition farthest from the
water closet. Where located in the side wall or partition, the door opening
shall be 4 inches (100 mm) maximum from the front partition. The door shall
be self-closing. A door pull complying with 404.2.7 shall be placed on both
sides of the door near the latch. Toilet compartment doors shall not swing
into the minimum required compartment area. |
4.17.5 Doors.
Toilet stall doors, including door hardware, shall comply with 4.13. If
toilet stall approach is from the latch side of the stall door, clearance
between the door side of the stall and any obstruction may be reduced to a
minimum of 42 in (1065 mm) (Fig. 30). |
|||